MAKE : NRG GLOBAL MODEL : TUBULAR SIDE MOUNTED TYPE : WITHOUT ISOLATION VALVE FLUID : LIQUID TEMPERATURE : 150O C SPECIFIC GRAVITY / DENSITY : 0.7-1.2 VISCOSITY (OP / MAX) : 1 Cp WETTED PARTS (MOC) : SS304 CONNECTION FLANGE : MS SLIP ON TYPE CASING / GLASS PROTECTION: MS “C” TYPE CHANNEL OF 1 MM THICK TUBE : BOROSILICATE TRANSPARENT GLASS TUBE of 19 MM OD SCALE : ACRYLIC1 ENGRAVED OF 25 MM WIDTH WITH LC 5MM PACKING : 100 % PTFE GLAND PUSHER : PTFE VALVE TYPE : NA VALVE BODY : NA VENT PLUG : ½” SS304 BSP-M Stop Plug DRAIN PLUG : ½” SS304 BSP-M Stop Plug ACCESSOIRES : NA HYD TEST : 7 Kg/cm2 to Vacuum FASTENERS : SS304
“NRG’ make Float & Board Level Indicators are designed for an accurate, reliable & trouble free float operated technique used in large non -pressurized storage tanks
Direct Indication
The Float & Board Level Indicators consists of a float connected to a pointer through a rope via a set of pulleys. The pointer glides over a calibrated gauge board, positioned parallel to the tank. The float accurately follows liquid level variations in vertical direction. The horizontal float movement is as such, the pointer in ‘TOP POSITION’ when tank is ‘EMPTY’ and in ‘BOTTOM POSITION’ when ‘FULL’.
This is micro-processor based Donnelly Chute level Transmitter with isolated o/p (4-20 mA), 10nos digital optical o/p and 2 relay control .The instrument is field programmable and user friendly.
In this Instrument user can set sensor sensitivity, sensor level selection, sample delay time and relay set point etc. The user can set level 2-10 then instrument automatically tunes for o/p 4-20 mA and display 0-100%.
The instrument has five settable parameters like rL1,rL2,snt,trl,Lst. The Instrument reads input level in sequence 1 to 10 if misplaced any level then it will not show above levels.
Operations Manual – Donnelly Chute Level Transmitter with Modbus Communication Model M11 NX
Operations Manual – Donnelly Chute Level Transmitter with Modbus Communication Model M11 MAX
Parameters
Snt: Sensor Sensitivity adjustment
Lst: Level Sensor selection (2-10)
Trl: sample Delay adjustment
RL1 and rL2 : Relay set point (0-100)
snt(sensitivity adjustment Parameter)
In this parameter user can set sensitivity of every (1-10 sensor) level sensor through key pad. The sensor value can be set in this parameter 93(Max.) to (185min.) sensitivity and it is normally set 100 value of every sensor.
If snt set 93 then i/p led direct on without input connection.
Lst(level selection parameter)
The user can be set input level 2-10 then instrument automatically tune for o/p 4-20 mA and display 0-100%
Trl = 20 set
rL1,rL2 : Relay set point value
Terminal Details
S1 to S10 : i/p for probe type level sensor
GND : Common terminal of probe sensor (Donnelly chute sensor)
L1 to L10 :o/p for isolated digital out put to plc
+24vdc : +v common (+24 vdc) for plc digital i/p
O/p 4-20 mA : mA output (isolated)
P : common terminal of Relay
N/O : Normaly open terminal of Relay
N/C : Normaly close terminal of relay
L : Phase of 220v AC @50/60Hz
N : Neutral
E : Earth
Specifications
Main (auxiliary supply) : 220vAc +-15% @50 Hz
O/P (Analog) : isolated 4-20mA
O/p (digital : isolated digital output (L1 to L10)
Relay set value : 000-100 settable
Display range : 0-100% according select sensor level (2-10) settable
Time delay setting : 001-100 ms settable
Input :10nos. Probe sensor (digital i/p)
Digital i/p / o/p : Indicate by LED as fitted on the front panel
LED : Red Led for i/p, Green Led optical digital o/p
Control Relay : one pair normally open potential free contact: @ 5A at 240v AC
Overall size : 96x194x223 mm (WxHxD )
Panel cutout : 184X92mm(HxW)
Configuration
1st press both PRG+ DN key for 5 seconds then display rL1 press ENT key
display last load value if change then Use up/dn key and press ENT key
display rL2 press ENT key display last load value if change then use up/dn key And press ENT key
display snt press ENT display 001(it means level 1 select to adjust sensitivity) press ENT
display last load value of sensor 1 sensitivity , if you want change value then use up/dn if value decrees (it means sensitivity higher side(93 max.) ) if value increase (it means sensitivity lower side(185 min.) if you want to store modified value then press and hold PRG key after press ENT key now release both key now modified value has been stored .
If you do not want to change in this parameter then use only ENT key, if press only ENT key it means by pass snt parameter, if press PRG key and ENT key it means modified value stored and display snt for next level sensor sensitivity calibration And same process apply for level 1 to level 10 after that, Next parameter Lst display press ENT key display last level select if change (2-10) then use up/dn key press ENT key display trL press ENT key display last value and set 20 and press ENT key and now exit configuration mode.